Power Supply
Utilising state of the
art switched mode power supply |
8-40 V DC (With
reverse polarity protection) |
| Current
Consumption |
40mA to 60mA
depending on input voltage. (46 mA @ 18VDC) |
| Operating
Temperature |
-5 to 40?C (If
used in standard enclosure) |
| SCADA Interface |
Conitel software
configurable interface. Two or four wire interface. Terminating or
non terminating line connection. Half Duplex. |
| Radio Interface |
Maxon 5W data
radio standard, others on request. |
| PCB Size |
108 mm x 105mm
(20 mm high) |
| Configuration
Port |
RS232 (D25) |
| Configuration
Tool |
Any 9600 baud
RS232 terminal emulator |
Configuration
Options
All configuration parameters
stored in EEPROM |
Station, Group,
Tx mark, Rx mark. External Rx gating, terminating/non-terminating
line and radio key enable. |
| Digital
Inputs |
7 digital inputs
with 50V optical isolation. (Not officially tested) MCD functions on inputs
one and two. |
| Analog
Inputs |
2 x 8 Bit analog
inputs. 0-1V input. Current shunt resistor option. Not isolated |
| Digital
Outputs |
Trip/Close clean
contact relay pair. 1A 120VAC/24VDC rating. |
| Standard
Enclosure |
APO41, L=30cm,
W=30cm, D=18cm. IP66 rated, UV stabilised. |
| Options |
Trip/Close Output
Relay expansion.
High common mode analog
input board (future)
Temperature sensor board,
-8 to 40ºC.
PLC logic functions. (Future).
Accumulator I/P.
Scan-In (Request to be Scanned)
facility.
230VAC power supply board.
Battery backup controller
board.
Maxon Synthesised VHF/UHF
data radio.
25W-VHF/15W-UHF Linear Amplifiers. |